韩国龙声电机株式会社4P2D电动转换开关的特点:
-保护继电器盘应用场 Applying place of protection relay
- T/L线路保护用配电盘 Protection panel for T/L railway line
-母线(BUS)保护用配电盘 Protection panel for BUS
-U.F.R保护用配电盘 Protection panel for U.F.R
-P.T电压被要求切换的系统电压 System voltage of requiring transference of
一本电动转换开关是在变电所的2重母线构造当中把母线P-T2次电压按照母线(B U S)的连接状态自
动切换,并供给保护继电器及器械用表,其它控制电压等的装置。可防止手动切换2次电压时发生的各种
机器的误动作,并以DC外部接点来有效地运用自动化及无人化(SCADA)的综合控制保护系统。
. 43PD Motor Cam Switch is equipment fO supply electric voltagefor control fO protection relay, meter ,control
power voltage, etc. due fO automatic transference Of BUS in accordance with connection state Of 2nd
voltage Of BUS P.T in substation double BUS structure. 43PD Moter Cam Switch protects occurring
malfunction Of equipment in case Of manual transference Of 2nd voltage.
This equipment appliesfor auto-control and SCADA of efficient application of total protection control system.
■保护继电器盘应用场所◆ < Applying place of protection relay◆
- T/L线路保护用配电盘 Protection panel for T/L railway line
一母线(BUS)保护用配电盘 Protection panel for BUS
-U.F.R保护用配电盘 Protection panel for U.F.R
-P.T电压被要求切换的系统电压 System voltage of requiring transference of P.T
-M.TR 154/23kv保护用配电盘 Protection panel for M.TR 154/23Kv
1-额定电压:250V,20A
2-最高使用电压:600V
3- DC开闭容量:DC125V,20A(时间常数50ms)
4-控制电源:DC125V(使用电压范围:DC94V-D C156V)
5-动作电流:1.0A以下
6-切换速度:输入外部信号後A->B或者B->A,P.T电压完全切换的时间在
2.5sec以内(供给额定控制电压DC125V时)
7-电压切换时间:开关动作之俊A->B或者B->A,P.T电压切换的时间
P.T无电压时间是2.5秒以内(供给额定控制电压DC125V时)
8-绝缘电阻:50MQ以上
9-寿命:20万次以上(动作1次後停5秒)